Product Details:
Brand Name: Macwey
Certification: Type Test Report
Model Number: VS1
Payment & Shipping Terms:
Minimum Order Quantity: 1
Price: > $800
Packaging Details: wooden case
Delivery Time: 10 working days
Payment Terms: T/T
Supply Ability: 5000
Detailed Product Description
Name: VS1 Vacuum Breaker Rated Voltage: 7.2, 12kV
Lightning Impulse Withstand Voltage: 75kV Rated Frequency: 50Hz
Rated Current: 630, 1250, 1600, 2000, 2500, 3150, 4000A Rated Short-time Withstand Current: 20, 25, 31.5, 40kA
Highlight:

Three Phase VS1 Vacuum Breaker

,

VS1 Vacuum Breaker 10kV

,

Three Phase 10kV Vacuum Circuit Breaker

VS1 10kV Vacuum Circuit Breaker with IEC Test Report
Product Introduction

The VS1 (ZN63A) series vacuum breaker is an indoor high voltage switchgear designed for 7.2kV/12kV three-phase power systems with 50Hz frequency. It provides reliable protection and control of electrical equipment, with particular suitability for frequent operation at rated current or continuous open circuit conditions due to its unique vacuum circuit breaker advantages.

Featuring an integrated spring operating mechanism and breaker body design, this unit can be installed as either a fixed unit or a withdrawable unit with a specially designed pushing framework. For installations requiring XGN2 or GG1A cabinets, the fixed type breaker can be equipped with additional interlock mechanisms.

Product Reference Standards

Manufactured in compliance with:

  • GB1984-89 Alternating Current High Voltage Breaker
  • JB3855-1996 3.6~40.5kV Indoor Alternating Current High Voltage Vacuum Breaker
  • DL403-1999 Specification for Order of 10~35kV Indoor High Voltage Vacuum Breaker
  • IEC56 (87 publication) requirements
Operating Environment Conditions
  • Temperature range: -15°C to +40°C
  • Humidity:
    • Daily average relative humidity ≤95%
    • Monthly average relative humidity ≤90%
    • Daily average saturated vapor pressure ≤2.2×10-3 MPa
    • Monthly average saturated vapor pressure ≤1.8×10-3 MPa
  • Altitude: Below 1000m
  • Earthquake resistance: Up to 8 magnitude
  • Must be installed away from moisture, fire hazards, explosive environments, chemical corrosion, and areas of excessive vibration
Technical Parameters
Item Unit Data
Rated voltage kV 7.2, 12
1 min power frequency withstand voltage kV 42
Lightning impulse withstand voltage kV 75
Rated frequency Hz 50
Rated current A 630, 1250, 1600, 2000, 2500, 3150, 4000
Rated short-time withstand current kA 20, 25, 31.5, 40
Rated withstand current (peak) kA 50, 63, 80, 100
Rated short-circuit opening current kA 20, 25, 31.5, 40
Rated short-circuit closing current kA 50, 63, 80, 100
Rated duration of short-circuit s 4
Rated operating sequence   O-0.3s-CO-180s-CO
Mechanical life times 10000, 30000